Plan Review Notes
Plan Review Notes For Permit 20050687
Permit Number 20050687
Review Stop E
Sequence Number 1
Notes
Date Text
2020-07-07 18:54:45ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN MUST BE DIIGITALLY SIGNED BY ENGINEER OR SIGNED
 BY THE ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE
 CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC 107.1
  
 2. NO VALUE SHOWN ON PERMIT APP.
  
 3. SATISFY ZONING COMMENTS.
  
 4. DISCONNECT MUST BE WITHIN SIGHT OF SIGN 600.6A1 NEC
  
 5. PROVIDE EXTERIOR LIGHTING CONTROLS AS SPECIFIED IN
 THE FBC ENERGY CONSERVATION. FBC EC C405.2.5
 EXTERIOR LIGHTING FOR BUILDING FACADE OR LANDSCAPE,
 MUST HAVE CONTROLS AUTOMATICALLY SET TO SHUT OFF
 LIGHTING PROGRAMMED FROM DAWN/DUSK. ALL TIME SWITCHES
 MUST HAVE MINIMUM 10HR BATTERY BACKUP.
  
 A PHOTOCELL AND TIMECLOCK AS SHOWN ON PLAN DOES NOT
 SUFFICE. IF ALL SIGNS ARE BEING CONTROLLED FROM A
 BUILDING MANAGMENT SYSTEM, A BLUE BIRD LIGHTING CONTROL
 CONTACTOR FOR EXAMPLE, ANNOTATE THAT ON THE PLAN.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  