2020-07-07 18:54:45 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PLAN MUST BE DIIGITALLY SIGNED BY ENGINEER OR SIGNED |
| BY THE ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE |
| CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC 107.1 |
| |
| 2. NO VALUE SHOWN ON PERMIT APP. |
| |
| 3. SATISFY ZONING COMMENTS. |
| |
| 4. DISCONNECT MUST BE WITHIN SIGHT OF SIGN 600.6A1 NEC |
| |
| 5. PROVIDE EXTERIOR LIGHTING CONTROLS AS SPECIFIED IN |
| THE FBC ENERGY CONSERVATION. FBC EC C405.2.5 |
| EXTERIOR LIGHTING FOR BUILDING FACADE OR LANDSCAPE, |
| MUST HAVE CONTROLS AUTOMATICALLY SET TO SHUT OFF |
| LIGHTING PROGRAMMED FROM DAWN/DUSK. ALL TIME SWITCHES |
| MUST HAVE MINIMUM 10HR BATTERY BACKUP. |
| |
| A PHOTOCELL AND TIMECLOCK AS SHOWN ON PLAN DOES NOT |
| SUFFICE. IF ALL SIGNS ARE BEING CONTROLLED FROM A |
| BUILDING MANAGMENT SYSTEM, A BLUE BIRD LIGHTING CONTROL |
| CONTACTOR FOR EXAMPLE, ANNOTATE THAT ON THE PLAN. |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO III |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| [email protected] |
| CELL: 561-657-1653 |
| |