2020-06-23 14:09:052017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20050685
 ADD: 2995 45TH ST. / RACE TRAC
 CONT: ATLAS SIGN HOLDINGS
 TEL: 561-863-6659
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 PERMIT FOR (2) NON-ILLUMINATED AWNINGS / VALUE OF
 $11,937.00. AWNINGS (AH) & (AI).
  
 1ST REVIEW
 DATE: TUES. JUNE 23RD/ 2020
 ACTION: DENIED
  
 1) THERE ARE SHEETS INCLUDED IN THIS PERMIT PACKAGE
 THAT HAVE NOTHING TO DO WITH THE 2 NON-ILLUMINATED
 AWNINGS, THEY NEED TO BE REMOVED OR BE MARKED VOID NOT
 PART OF THIS PERMIT. 107.2.1.2 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 2) SHEETS S-5 FOR AWNING A-I & SHEET S-6 FOR AWNING A-J
 BOTH SHOW THE STRUCTURAL FRAMEWORK OF THE AWNING BUT
 NOTHING IS INDICATED AS TO THE MATERIAL COVERING IS TO
 BE MADE FROM? FOR THIS REVIEW PURPOSE IT IS SUPPOSED TO
 BE A CLOTH MATERIAL. 2017 FBC-B SECTION 3105.3.4.1.
 MATERIALS. WHEN FABRIC IS USED TO COVER AWNINGS OR
 FABRIC OVER COVERED FRAMES SHALL MEET THE FLAME
 PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 OR HAVE A
 FLAME SPREAD INDEX NOT GREATER THAN 25 WHEN TESTED IN
 ACCORDANCE WITH ASTM E-84 OR UL 723.
  
 3) BOTH SHEETS S5 & S6 BOTH GIVE THE WIND DESIGN
 CRITERIA OF 170 VULT EXPOSURE C BUT THE PLANS DO NOT
 STATE IF THIS IS FOR THE BUILDING OR AWNINGS. PLEASE
 REVIEW THE 2 CODE SECTIONS BELOW FOR BREAKAWAY FABRIC
 OR PERMANENT NON-REMOVALABLE FABRIC.
  
 RIGID AWNINGS. BREAK AWAY FABRIC. FBC-B
 3105.4.2.1.DESIGN. THE WIND DESIGN LOADS FOR ANY FABRIC
 OR MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND
 VELOCITIES OF 75 MPH, SHALL BE BASED ON THE FOLLOWING
 CRITERIA:
 1) MINIMUM WIND SPEED OF 105 MPH
 2) EXPOSURES B, C, OR D AS DEFINED IN CHAPTER 16.
  
 RIGID AWNING. PERMANENT OR NON-REMOVABLE FABRIC. FBC-B
 3105.4.2.2. THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE COVERED STRUCTURE DESIGNED WITH A PERMANENT OR
 NON-REMOVABLE FABRIC OR MEMBRANE, SHALL BE BASED ON THE
 FOLLOWING CRITERIA:
 1) MINIMUM WIND SPEED VELOCITY AS REQUIRED IN CHAPTER
 16 USING FIGURE 1609.3(3) 150 VULT, CATEGORY 1
 BUILDINGS.
 2) EXPOSURES B, C, OR D AS DEFINED IN CHAPTER 16.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved