2020-06-23 14:09:05 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20050685 |
| ADD: 2995 45TH ST. / RACE TRAC |
| CONT: ATLAS SIGN HOLDINGS |
| TEL: 561-863-6659 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| PERMIT FOR (2) NON-ILLUMINATED AWNINGS / VALUE OF |
| $11,937.00. AWNINGS (AH) & (AI). |
| |
| 1ST REVIEW |
| DATE: TUES. JUNE 23RD/ 2020 |
| ACTION: DENIED |
| |
| 1) THERE ARE SHEETS INCLUDED IN THIS PERMIT PACKAGE |
| THAT HAVE NOTHING TO DO WITH THE 2 NON-ILLUMINATED |
| AWNINGS, THEY NEED TO BE REMOVED OR BE MARKED VOID NOT |
| PART OF THIS PERMIT. 107.2.1.2 ADDITIONAL INFORMATION |
| IS REQUIRED. |
| |
| 2) SHEETS S-5 FOR AWNING A-I & SHEET S-6 FOR AWNING A-J |
| BOTH SHOW THE STRUCTURAL FRAMEWORK OF THE AWNING BUT |
| NOTHING IS INDICATED AS TO THE MATERIAL COVERING IS TO |
| BE MADE FROM? FOR THIS REVIEW PURPOSE IT IS SUPPOSED TO |
| BE A CLOTH MATERIAL. 2017 FBC-B SECTION 3105.3.4.1. |
| MATERIALS. WHEN FABRIC IS USED TO COVER AWNINGS OR |
| FABRIC OVER COVERED FRAMES SHALL MEET THE FLAME |
| PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 OR HAVE A |
| FLAME SPREAD INDEX NOT GREATER THAN 25 WHEN TESTED IN |
| ACCORDANCE WITH ASTM E-84 OR UL 723. |
| |
| 3) BOTH SHEETS S5 & S6 BOTH GIVE THE WIND DESIGN |
| CRITERIA OF 170 VULT EXPOSURE C BUT THE PLANS DO NOT |
| STATE IF THIS IS FOR THE BUILDING OR AWNINGS. PLEASE |
| REVIEW THE 2 CODE SECTIONS BELOW FOR BREAKAWAY FABRIC |
| OR PERMANENT NON-REMOVALABLE FABRIC. |
| |
| RIGID AWNINGS. BREAK AWAY FABRIC. FBC-B |
| 3105.4.2.1.DESIGN. THE WIND DESIGN LOADS FOR ANY FABRIC |
| OR MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK |
| REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND |
| VELOCITIES OF 75 MPH, SHALL BE BASED ON THE FOLLOWING |
| CRITERIA: |
| 1) MINIMUM WIND SPEED OF 105 MPH |
| 2) EXPOSURES B, C, OR D AS DEFINED IN CHAPTER 16. |
| |
| RIGID AWNING. PERMANENT OR NON-REMOVABLE FABRIC. FBC-B |
| 3105.4.2.2. THE WIND DESIGN LOADS FOR ANY FABRIC OR |
| MEMBRANE COVERED STRUCTURE DESIGNED WITH A PERMANENT OR |
| NON-REMOVABLE FABRIC OR MEMBRANE, SHALL BE BASED ON THE |
| FOLLOWING CRITERIA: |
| 1) MINIMUM WIND SPEED VELOCITY AS REQUIRED IN CHAPTER |
| 16 USING FIGURE 1609.3(3) 150 VULT, CATEGORY 1 |
| BUILDINGS. |
| 2) EXPOSURES B, C, OR D AS DEFINED IN CHAPTER 16. |
| |
| 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |