2020-05-29 16:48:59RESIDENTIAL (R2) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 FLOORING UNDERLAYMENT
 1- SOUND INSULATION MATERIAL SUBMITTED:
 A) PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
  
 B) PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC)
 TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY
 SEC. 1207.2 OF FBC 6TH EDITION (2017).
 NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE
 ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING.
  
 C) PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC)
 TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY
 SEC. 1207.3 OF FBC 6TH EDITION (2017).
 NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE
 ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. (NOTE: SUBMIT OLD DRAWINGS FOR REFERENCE). A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,