2020-05-29 16:48:59 | RESIDENTIAL (R2) BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| SHALL COMPLY WITH THE MATERIALS AND METHODS |
| REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| |
| FLOORING UNDERLAYMENT |
| 1- SOUND INSULATION MATERIAL SUBMITTED: |
| A) PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE |
| DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION |
| (2017). |
| |
| B) PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC) |
| TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY |
| SEC. 1207.2 OF FBC 6TH EDITION (2017). |
| NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE |
| ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT |
| ACOUSTICAL CEILING. |
| |
| C) PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC) |
| TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY |
| SEC. 1207.3 OF FBC 6TH EDITION (2017). |
| NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE |
| ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT |
| ACOUSTICAL CEILING. |
| |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. (NOTE: SUBMIT OLD DRAWINGS FOR REFERENCE). A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |