2020-05-29 15:48:241ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20050598
  
 CODES IN EFFECT:
  
 FB FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE COMPLETED ENERGY GAUGE FORM R405. FBC
 EC R403.7.1
  
 2) PLEASE PROVIDE SPECS ON THE RANGE AND THE HOOD. FBC
 FS 107.2.1
  
 3) SHEET M-1: NOTE 5 CALLS FOR THE HOOD EXHAUST DUCT TO
 GO OUT THRU THE ROOF. PLEASE PROVIDE A DETAIL DRAWING
 OF THIS GOING THROUGH THE FLOOR AND BEDROOM ABOVE. FBC
 FS 107.2.1
  
 4) PLEASE PROVIDE A DETAIL DRAWING OF THE APPLIANCE
 ANCHORAGE DESIGN. FBC RES M1307.2
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  