Plan Review Notes For Permit 20050598 |
Permit Number |
20050598 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-05-29 15:48:24 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT-20050598 | | | | CODES IN EFFECT: | | | | FB FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE PROVIDE COMPLETED ENERGY GAUGE FORM R405. FBC | | EC R403.7.1 | | | | 2) PLEASE PROVIDE SPECS ON THE RANGE AND THE HOOD. FBC | | FS 107.2.1 | | | | 3) SHEET M-1: NOTE 5 CALLS FOR THE HOOD EXHAUST DUCT TO | | GO OUT THRU THE ROOF. PLEASE PROVIDE A DETAIL DRAWING | | OF THIS GOING THROUGH THE FLOOR AND BEDROOM ABOVE. FBC | | FS 107.2.1 | | | | 4) PLEASE PROVIDE A DETAIL DRAWING OF THE APPLIANCE | | ANCHORAGE DESIGN. FBC RES M1307.2 | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|