2020-06-04 15:06:33 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20050572 |
| |
| CODES IN EFFECT: |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE SPEC SHEETS FOR THE RV61 REGULATOR. |
| SHOW THAT THIS REGULATOR MEETS ANSI Z21.80. FBC RES |
| G2421.1 |
| |
| 2) EXISTING REGULATOR AT THE METER IS A LOW PRESSURE |
| REGULATOR. THE ?? GALV. UTILITY RISERS MUST BE SIZED TO |
| CARRY THE EXISTING LOAD AND THE ADDITIONAL LOAD OF THE |
| GENERATOR. PLEASE PROVIDE THE TABLE USED TO SIZE THIS |
| AREA. THE NEW LOAD FOR THE PIPING IS 802,000 BTU?S. FBC |
| RES G2421.4 |
| |
| 3) PLEASE PROVIDE THE LENGTH OF POLY UNDERGROUND |
| PIPING. FBC FS 107.2.1 |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |