2020-06-05 13:12:55 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20050567 |
| |
| CODES IN EFFECT: |
| |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THIS APPEARS TO BE A LOW PRESSURE SYSTEM. THE ?? |
| RISER LEAVING THE METER MUST BE ABLE TO HANDLE THE |
| EXISTING AND NEW LOADS ADDED. THIS IS A SFR SO THE 2017 |
| FLORIDA RESIDENTIAL BUILDING CODE MUST BE USED. TABLE |
| G2413.4(1) IS FOR 0.5? W.C PRESSURE DROP. THIS TABLE |
| INDICATES THAT THIS ?? PIPE WILL ONLY SUPPORT 360,000 |
| BTU?S THIS PIPE IS SUPPLYING THE ENTIRE SYSTEM WHICH IS |
| 457,000BTU?S. TFBC G2412.4 |
| |
| 2) PLEASE LABEL EACH PIPE SIZE ALONG THIS SYSTEM. WHERE |
| IS THE 1 ?? TRANSITION? FBC FS 107.2.1 |
| |
| 3) AT THE ABOVE MENTIONED 0.5? PRESSURE DROP THE ??X2? |
| FLEXIBLE FUEL LINE WILL ONLY SUPPLY 290,900 BTU?S TO |
| THE GENERATOR. PLEASE ADJUST THE SIZE OF FLEX HOSE TO |
| SUPPLY THE REQUIRED 327,000BTU?S. FBC FS 107.2.1 |
| |
| 4) PLEASE PROVIDE THE SPEC SHEETS FOR THE RV61 |
| REGULATOR SHOWN ON THE DRAWING. FBC FS 107.2.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |