Plan Review Notes For Permit 20050565 |
Permit Number |
20050565 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-06-04 12:28:21 | GAS LINE IS APPROVED WITH A NOTE: IT APPEARS THE GAS | | LINE FROM THE T FITTING AFTER THE METER TO THE | | REGULATOR AT THE GENERATOR IS A 2 LB SYSTEM. THE | | DRAWING INDICATED TO USE TABLE 402.4(3). THIS IS THE | | WRONG TABLE AS IT IS FOR A LOW PRESSURE SYSTEM. THE | | CORRECT TABLE IS 402.4(5). |
|