Plan Review Notes
Plan Review Notes For Permit 20050565
Permit Number 20050565
Review Stop G
Sequence Number 1
Notes
Date Text
2020-06-04 12:28:21GAS LINE IS APPROVED WITH A NOTE: IT APPEARS THE GAS
 LINE FROM THE T FITTING AFTER THE METER TO THE
 REGULATOR AT THE GENERATOR IS A 2 LB SYSTEM. THE
 DRAWING INDICATED TO USE TABLE 402.4(3). THIS IS THE
 WRONG TABLE AS IT IS FOR A LOW PRESSURE SYSTEM. THE
 CORRECT TABLE IS 402.4(5).