Plan Review Notes
Plan Review Notes For Permit 20050561
Permit Number 20050561
Review Stop P
Sequence Number 1
Notes
Date Text
2020-06-12 11:10:30PLAN REVIEW - PLUMBING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SANITARY RISER SHOWS TWO TUBS. PLUMBING PLAN SHOWS
 ONE TUB AND ONE SHOWER.
 107.2 CONSTRUCTION DOCUMENTS.
  
 2. PROVIDE THE FOLLOWING STATEMENT IN PLUMBING NOTES
 FOR SHOWER VALVES -
 P2708.4SHOWER CONTROL VALVES. INDIVIDUAL SHOWER AND
 TUB/ SHOWER COMBINATION VALVES SHALL BE EQUIPPED WITH
 CONTROL VALVES OF THE PRESSURE-BALANCE,
 THERMOSTATIC-MIXING OR COMBINATION
 PRESSURE-BALANCE/THERMOSTATIC-MIXING VALVE TYPES WITH A
 HIGH LIMIT STOP IN ACCORDANCE WITH ASSE 1016/ASME
 A112.1016/CSA B125.16. THE HIGH LIMIT STOP SHALL BE SET
 TO LIMIT THE WATER TEMPERATURE TO NOT GREATER THAN
 120?F (49?C). IN-LINE THERMOSTATIC VALVES SHALL NOT BE
 USED FOR COMPLIANCE WITH THIS SECTION.
  
 3. SANITARY RISER SHOWS A DOUBLE SINK IN ONE BATH
 GROUP. PLUMBING PLAN SHOWS SINGLE LAV. IN EACH BATH
 GROUP.
 107.2 CONSTRUCTION DOCUMENTS.
  
 4. PROVIDE WATER DISTRIBUTION RISER DIAGRAHM.
 P2903.1WATER SUPPLY SYSTEM DESIGN CRITERIA. THE WATER
 SERVICE AND WATER DISTRIBUTION SYSTEMS SHALL BE
 DESIGNED, AND PIPE SIZES SHALL BE SELECTED SUCH THAT
 UNDER CONDITIONS OF PEAK DEMAND, THE CAPACITIES AT THE
 POINT OF OUTLET DISCHARGE SHALL NOT BE LESS THAN SHOWN
 IN TABLE P2903.1.
  
 5. PROVIDE DEMENSIONS TO SHOWER PAN DETAIL PER P2709.1
 AND P2709.2
 P2709.1 SHOWER PAN CONSTRUCTION. FBC 107.2.1
 WHERE A SHOWER RECEPTOR HAS A FINISHED CURB THRESHOLD,
 IT SHALL BE NOT LESS THAN 1 INCH (25 MM) BELOW THE
 SIDES AND BACK OF THE RECEPTOR. THE CURB SHALL BE NOT
 LESS THAN 2 INCHES (51 MM) AND NOT MORE THAN 9 INCHES
 (229 MM) DEEP WHEN MEASURED FROM THE TOP OF THE CURB TO
 THE TOP OF THE DRAIN. THE FINISHED FLOOR SHALL SLOPE
 UNIFORMLY TOWARD THE DRAIN NOT LESS THAN 1/4 UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE) NOR
 MORE THAN 1/2 UNIT VERTICAL PER 12 UNITS HORIZONTAL
 (4-PERCENT SLOPE) AND FLOOR DRAINS SHALL BE FLANGED TO
 PROVIDE A WATER-TIGHT JOINT IN THE FLOOR.
 P2709.3 SHOWER PAN LINING INSTALLATION.
 LINING MATERIALS SHALL BE SLOPED ONE FOURTH UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE) TO
 WEEP HOLES IN THE SUBDRAIN BY MEANS OF A SMOOTH,
 SOLIDLY FORMED SUBBASE, SHALL BE PROPERLY RECESSED AND
 FASTENED TO APPROVED BACKING SO AS NOT TO OCCUPY THE
 SPACE REQUIRED FOR THE WALL COVERING, AND SHALL NOT BE
 NAILED OR PERFORATED AT ANY POINT LESS THAN 1 INCH
 (25.4 MM) ABOVE THE FINISHED THRESHOLD.
  
  
  
  
  