2020-07-09 14:43:47PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 FBC 107
 1) THE GENERATOR PAD ENGINEERING THAT WAS SUBMITTED IS
 NOT ACCEPTABLE FOR THE FOLLOWING REASONS:
 A) THE SCHEDULE ON THE DRAWINGS SPECIFIES THE REQUIRED
 MINIMUM WEIGHT FOR THE 22KW GENERATOR AS 466 LBS. AND
 THE SPECIFICATIONS FOR YOUR GENERATOR HAS A WEIGHT OF
 445 LBS.
 B) THE SCHEDULE ON THE DRAWINGS SPECIFIES THE ALLOWABLE
 WIND LOAD PRESSURES FOR THE GENERATOR, BUT THE REQUIRED
 WIND LOAD PRESSURES FOR THE SITE IT WILL BE INSTALLED
 ARE NOT PROVIDED. SEE GENERAL NOTE #2 ON THE DRAWING
 THAT STATES THAT THE REQUIRED PRESSURES FOR THE SITE OR
 TO BE DETERMINED BY OTHERS.