2020-06-16 13:38:09 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20050520 |
| |
| CODES IN EFFECT: |
| |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) MASTER PROJECT NUMBER 20030300 DOES NOT LIST A GAS |
| REVIEW. PLEASE SUBMIT THE GAS PERMIT APPLICATION FOR |
| THIS PROJECT. FBC FS 107.2.1 |
| |
| 2) PLEASE PROVIDE GAS TABLE NUMBERS USED TO SIZE THIS |
| SYSTEM. FBC FS 107.2.1 |
| |
| 3) WORDING ABOUT THE NEW GALV. PIPE AT METER ON THE |
| BOTTOM OF THE PAGE HAS BEEN CUT OFF. PLEASE REWORK THIS |
| AREA SO WE CAN READ THE COMMENT. PLEASE SHOW A DETAIL |
| DRAWING OF THE METER AND ALL THE CONNECTIONS TO IT, |
| INCLUDE PIPE SIZES AND MATERIAL. FBC FS 107.2.1. |
| |
| 4) PLEASE PROVIDE SPEC SHEETS ON THE GENERATOR AND NEW |
| REGULATORS USED FOR THIS PROJECT. INCLUDE MODEL |
| NUMBERS. FBC FS 107.2.1 |
| |
| 5) HOW IS GAS CONNECTING TO GENERATOR? IF USING A FLEX |
| HOSE PLEASE SUBMIT SPEC SHEET ALONG WITH THE SIZE AND |
| LENGTH OF HOSE. VERIFY WHICH PRESSURE DROP WILL BE USED |
| ON THE SPEC SHEET. FBC FS 107.2.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |