2020-06-10 09:19:41PLAN
 REVIEW COMMENTS
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE APPLICATION STATES THAT THIS WILL BE A RE-COVER
 RATHER THAN A TEAR OFF. IN ORDER TO DO A RE-COVER THERE
 CAN BE ONLY ONE EXISTING ROOF COVERING AND IT HAS TO BE
 IN GOOD ENOUGH CONDITION TO RECOVER. THE EXISTING ROOF
 WILL HAVE TO BE INSPECTED AND APPROVED BY THE BUILDING
 DEPARTMENT BEFORE IT CAN BE COVERED. FBC 107
  
 2) THE ROOFING SYSTEM ON PAGE 65 OF NOA NO. 15-1020.02,
 IS NOT FOR A WOOD ROOF DECK AND THE DESIGN PRESSURE OF
 -45 PSF IS TOO LOW. THE DESIGN PRESSURE FOR THIS SYSTEM
 HAS LIMITATION #9 AND CAN NOT BE INCREASED BY ENHANCED
 FASTENING. FBC 107
  
 3) CIRCLE OR HI-LIGHT THE ROOFING SYSTEM AND DESIGN
 PRESSURE OF THE ONE THAT YOU WILL BE USING. THIS ONE
 STORY BUILDING IS LOCATED IN A 170 MPH VULT WINDSPEED
 AND IS EXPOSURE CATEGORY C. SELECT A SYSTEM THAT HAS A
 DESIGN PRESSURE OF - 95.7 PSF OR MORE OR ONE WITH
 LIMITATION #7 THAT ALLOWS ENHANCED FASTENING
 CALULATIONS. IF USING ENHANCED FASTENING THE
 CALULATIONS ARE REQUIRED TO BE SIGNED AND SEALED. FBC
 R301
  
  
  