Plan Review Notes For Permit 20050511 |
Permit Number |
20050511 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-06-10 09:19:41 | PLAN | | REVIEW COMMENTS | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE APPLICATION STATES THAT THIS WILL BE A RE-COVER | | RATHER THAN A TEAR OFF. IN ORDER TO DO A RE-COVER THERE | | CAN BE ONLY ONE EXISTING ROOF COVERING AND IT HAS TO BE | | IN GOOD ENOUGH CONDITION TO RECOVER. THE EXISTING ROOF | | WILL HAVE TO BE INSPECTED AND APPROVED BY THE BUILDING | | DEPARTMENT BEFORE IT CAN BE COVERED. FBC 107 | | | | 2) THE ROOFING SYSTEM ON PAGE 65 OF NOA NO. 15-1020.02, | | IS NOT FOR A WOOD ROOF DECK AND THE DESIGN PRESSURE OF | | -45 PSF IS TOO LOW. THE DESIGN PRESSURE FOR THIS SYSTEM | | HAS LIMITATION #9 AND CAN NOT BE INCREASED BY ENHANCED | | FASTENING. FBC 107 | | | | 3) CIRCLE OR HI-LIGHT THE ROOFING SYSTEM AND DESIGN | | PRESSURE OF THE ONE THAT YOU WILL BE USING. THIS ONE | | STORY BUILDING IS LOCATED IN A 170 MPH VULT WINDSPEED | | AND IS EXPOSURE CATEGORY C. SELECT A SYSTEM THAT HAS A | | DESIGN PRESSURE OF - 95.7 PSF OR MORE OR ONE WITH | | LIMITATION #7 THAT ALLOWS ENHANCED FASTENING | | CALULATIONS. IF USING ENHANCED FASTENING THE | | CALULATIONS ARE REQUIRED TO BE SIGNED AND SEALED. FBC | | R301 | | | | | | |
|