2020-06-03 15:09:31PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE APPLICATION STATES THAT THIS WILL BE A RE-COVER
 RATHER THAN A TEAR OFF. IN ORDER TO DO A RE-COVER THERE
 CAN BE ONLY ONE EXISTING ROOF COVERING AND IT HAS TO BE
 IN GOOD ENOUGH CONDITION TO RECOVER. THE EXISTING ROOF
 WILL HAVE TO BE INSPECTED AND APPROVED BY THE BUILDING
 DEPARTMENT BEFORE IT CAN BE COVERED. FBC 107
  
 2) THE W-5 SYSTEM THAT YOU HIGHLITED IN THE FL16709
 PRODUCT APPROVAL IS FOR NEW CONSTRUCTION OR RE-ROOF
 (TEAR OFF). IT IS NOT FOR RECOVER. ALL OF THE RECOVER
 SYSTEMS IN THIS PRODUCT APPROVAL REQUIRE AN INSULATION
 LAYER. FBC 107..2.1
  
 3) REGARDLESS OF THE ROOFING SYSTEM THAT YOU SELECT IT
 WILL HAVE TO BE INSTALLED AS SPECIFIED IN THE PRODUCT
 APPROVAL AND THE REQUIRED DESIGN PRESSURES MUST BE MET.
 FBC R301
  
 4) THE VALUE OF $3000.00 APPEARS TO BE LOW. SUBMIT A
 COPY OF THE SIGNED CONTRACT. FBC 109.3
  
 5) SPECIFY THE AREA OF THE ROOF AND THE ROOF MEAN
 HEIGHT. FBC 107
  