2020-06-26 10:04:48RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL2533-R23
 SUBMITTED:
 A) SELECTED ASSEMBLY W-62 DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES. NEED TO PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY NOTE #9
 ON PAGE 3 OF 67 OF PRODUCT APPROVAL SUBMITTED. NEED THE
 CALCULATIONS TO MEET THE DESIGN PRESSURES REQUIRED BY
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,