Plan Review Notes
Plan Review Notes For Permit 20050504
Permit Number 20050504
Review Stop G
Sequence Number 2
Notes
Date Text
2020-08-26 16:27:322ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20050504
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THIS IS AN ADDITION TO AN EXISTING GAS LINE. WE NEED TO
 MAKE SURE THAT THE EXISTING GAS LINE CAN SUPPORT THE
 ADDITIONAL 330,000 BTU?S FOR THE NEW GENERATOR. FOR
 THIS WE NEED THE DEVELOPED LENGTH TO THE MOST REMOTE
 GAS APPLIANCE. THIS COULD BE EITHER ON THE EXISTING GAS
 LINE OR IT COULD BE THE NEW GAS LINE IF IT BECOMES THE
 MOST REMOTE APPLIANCE ON THE GAS LINE. WE ALSO NEED THE
 OPERATING PRESSURE OF THE EXISTING SYSTEM. I CANNOT
 SIZE THE NEW LINE UNTIL I HAVE THIS INFORMATION.
  
 1) GAS TABLE PROVIDED IS FOR A 2PSI SYSTEM BUT THE GAS
 RISER DIAGRAM INDICATES THE NEW PIPING IS 12? WC.
 PLEASE PROVIDE CORRECTED INFORMATION. FBC FS 107.2.1
  
 2) PLEASE INDICATE NEW PIPING MATERIAL ON THE RISER
 DIAGRAM. FBC FS 107.2.1
  
 3) PLEASE SPECIFY EXISTING GAS METER?S OPERATING
 PRESSURE AND PIPE MATERIAL AND SIZE OF EXISTING PIPE
 LEAVING THE METER ( THE PIPE THAT YOU SPLICE INTO). FBC
 FS 107.2.1
  
 4) PLEASE PROVIDE THE LONGEST DEVELOPED LENGTH TO THE
 MOST REMOTE APPLIANCE ON THIS GAS LINE. FBC FS 107.2.1
  
 5) PROVIDE SPEC SHEETS ON REGULATORS USED AND SHOW THEY
 ON THE GAS RISER DIAGRAM. FBC FS 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  