2020-06-12 13:33:38 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20050504 |
| |
| CODES IN EFFECT: |
| |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| PERMIT #05060682 ISSUED JUNE 08-2005 WAS A PERMIT FOR |
| INTERIOR AND EXTERIOR GAS LINE SYSTEM. THIS SUBMISSION |
| DOES NOT SHOW ANY EXISTING GAS LINE FOR THIS PROJECT. |
| PLEASE PROVIDE A COMPLETE GAS LINE DIAGRAM SHOWING ALL |
| THE EXISTING APPLIANCES AND GAS LINES. INCLUDE PIPE |
| MATERIAL AND PIPE SIZES ALONG WITH ANY REGULATORS AND |
| GAS PRESSURES FOR THE ENTIRE SYSTEM. PLEASE SHOW A |
| DETAIL OF THE CONNECTION OF THE NEW GAS LINE FOR THE |
| GENERATOR TO THE EXISTING GAS LINE. |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |