2020-06-12 13:33:381ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20050504
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 PERMIT #05060682 ISSUED JUNE 08-2005 WAS A PERMIT FOR
 INTERIOR AND EXTERIOR GAS LINE SYSTEM. THIS SUBMISSION
 DOES NOT SHOW ANY EXISTING GAS LINE FOR THIS PROJECT.
 PLEASE PROVIDE A COMPLETE GAS LINE DIAGRAM SHOWING ALL
 THE EXISTING APPLIANCES AND GAS LINES. INCLUDE PIPE
 MATERIAL AND PIPE SIZES ALONG WITH ANY REGULATORS AND
 GAS PRESSURES FOR THE ENTIRE SYSTEM. PLEASE SHOW A
 DETAIL OF THE CONNECTION OF THE NEW GAS LINE FOR THE
 GENERATOR TO THE EXISTING GAS LINE.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  