Date |
Text |
2020-08-03 14:36:58 | PLAN |
| REVIEW COMMENTS |
| |
| 2ND REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| COMMENTS FOR THE PREVIOUS REVIEW WERE NOT ADDRESSED. |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| FBC 107 |
| 1) THE GENERATOR PAD ENGINEERING THAT WAS SUBMITTED IS |
| NOT ACCEPTABLE FOR THE FOLLOWING REASONS: |
| A) THE SCHEDULE ON THE DRAWINGS SPECIFIES THE REQUIRED |
| MINIMUM WEIGHT FOR THE 22KW GENERATOR AS 466 LBS. AND |
| THE SPECIFICATIONS FOR YOUR GENERATOR HAS A WEIGHT OF |
| 445 LBS. |
| B) THE SCHEDULE ON THE DRAWINGS SPECIFIES THE ALLOWABLE |
| WIND LOAD PRESSURES FOR THE GENERATOR, BUT THE REQUIRED |
| WIND LOAD PRESSURES FOR THE SITE IT WILL BE INSTALLED |
| ARE NOT PROVIDED. SEE GENERAL NOTE #2 ON THE DRAWING |
| THAT STATES THAT THE REQUIRED PRESSURES FOR THE SITE OR |
| TO BE DETERMINED BY OTHERS. |
2020-08-03 14:31:30 | PLAN REVIEW GENERATOR - BUILDING |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| GENERATOR PAD |
| |
| 1) STRUCTURAL DETAIL OF THE PRE-CAST GENERATOR PAD |
| SHALL HAVE A VALID DIGITAL SIGNATURE OF THE DESIGN |
| PROFESSIONAL PER FS 471 & FAC 61G15. |
| 2) PROVIDE WIND DESIGN LOADS FOR THE GENERATOR WITH A |
| VALID DIGITAL SIGNATURE OF THE DESIGN PROFESSIONAL AS |
| REQUIRED FOR THE GENERATOR PAD ENGINEERING PER FBC |
| 107.3.5.3 AND R301.2. |
| |