2020-06-17 12:47:08 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20050502 |
| |
| CODES IN EFFECT: |
| |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THIS IS AN EXISTING GAS METER, I CANNOT REVIEW THIS |
| PROJECT UNTIL THE ENTIRE GAS SYSTEM HAS BEEN SUBMITTED. |
| PLEASE SUBMIT A LEGIBLE DRAWING SHOWING GAS PRESSURE OF |
| THE CURRENT EXISTING GAS SYSTEM, A HOUSE LAYOUT WITH |
| THE GAS LINES SHOWN. PLEASE INCLUDE ALL REGULATORS AND |
| SHUT OFF VALVES. PROVIDE THE SPECS FOR THE REGULATORS |
| USED. PROVIDE PIPE SIZES, TYPE OF MATERIAL USED. PLEASE |
| ALSO INCLUDE THE GAS TABLE NUMBER USED FOR EACH TYPE OF |
| PIPING IN THIS SYSTEM. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |