2020-06-17 11:07:49 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20050500 |
| |
| CODES IN EFFECT: |
| |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE GAS PLAN SHOWS AN EXISTING GAS METER, I CANNOT |
| REVIEW THIS PROJECT UNTIL THE ENTIRE GAS SYSTEM HAS |
| BEEN SUBMITTED. PLEASE SUBMIT A LEGIBLE DRAWING SHOWING |
| GAS PRESSURE OF THE CURRENT EXISTING GAS SYSTEM, A |
| HOUSE LAYOUT WITH THE GAS LINES SHOWN. PLEASE INCLUDE |
| ALL REGULATORS AND SHUT OFF VALVES. PROVIDE THE SPECS |
| FOR THE REGULATORS USED. PROVIDE PIPE SIZES, TYPE OF |
| MATERIAL USED. PLEASE ALSO INCLUDE THE GAS TABLE NUMBER |
| USED FOR EACH TYPE OF PIPING IN THIS SYSTEM. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |