Plan Review Notes
Plan Review Notes For Permit 20050421
Permit Number 20050421
Review Stop B
Sequence Number 1
Notes
Date Text
2020-05-18 10:21:14ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT
 APPROVAL REQUIRES ADDITIONAL SIGNED AND SEALED
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE
 THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL (-52.5)
 - SEE GENERAL LIMITATION NUMBER 7 ON THE PRODUCT
 APPROVAL. SIGNED AND SEALED DRAWINGS OR DOCUMENTS WILL
 NEED TO BE DIGITALLY SIGNED AND SEALED TO BE USED IN
 ELECTRONIC PLAN REVIEW.
  
 FYI - ENGINEER CANNOT SELF-CERTIFY THE DIGITAL
 SIGNATURE
 668.003(2) AND (3), F.S.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING
 PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL HAVE
 THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION
 AUTHORITY.
  