2020-08-06 07:35:04 | 2ND REVIEW FBC-2017 MECHANICAL |
| PERMIT-20050410 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE DATURA OCCUPANCY PERMIT APPLICATION SUBMITTED IS |
| REQUESTING A HIGHER OCCUPANCY GOING FROM 93 TO 166 |
| OCCUPANTS. THE SUBMITTED MECHANICAL DOCUMENTS ? DATURA |
| BAR UPDATED LOADS PER NEW OCCUPANCY? INDICATES THAT |
| RTTU-1 IS SIZED FOR 26 OCCUPANTS; RTU-2 IS SIZED FOR 58 |
| OCCUPANTS; AND RTU-3 IS SIZED FOR 61 OCCUPANTS. |
| THEREFORE THE OCCUPANT LOAD FOR THESE SYSTEMS COMBINED |
| IS FOR 145 OCCUPANTS. BASED ON THE SUBMITTED MECHANICAL |
| SYSTEM CALCULATIONS THIS PROJECT WILL ONLY SUPPORT A |
| TOTAL OF 145 OCCUPANTS NOT 166 OCCUPANTS. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |
| MICHAEL EDWARDS |
| MECHANICAL EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL. 33401 |
| 561-805-6728 |
| [email protected] |
| |