Plan Review Notes
Plan Review Notes For Permit 20050388
Permit Number 20050388
Review Stop B
Sequence Number 1
Notes
Date Text
2020-05-22 16:28:36PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS IS A COMMERCIAL BUILDING AND THE WINDLOAD
 CALCULATIONS THAT WERE SUBMITTED ARE FROM THE FBC
 RESIDENTIAL CODE BOOK. THE WINDLOAD CALCULATIONS ARE
 REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL. FBC 1609
  
 2) THE DEFAULT EXPOSURE CATEGORY IS C FOR THE CITY OF
 WEST PALM BEACH. IF YOU WISH TO USE EXPOSURE B, YOU
 WILL NEED TO SUBMIT AN ANALYSIS FROM A FLORIDA LICENSED
 DESIGN PROFESSIONAL. FBC BUILDING 1609
  
 3) SUBMIT AN ELEVATION DRAWING OF THE THE STOREFRONT
 SYSTEM THAT WILL BE INSTALLED.THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DRAWING IS REQUIRED TO
 BE ON THE DRAWING. FBC 107.2.1.2
  
 4) INDICATE THE SPECIFIC ITEMS, SUCH AS, SIZE AND
 MAXIMUM DESIGN PRESSURE THAT APPLY TO THIS PROJECT IN
 THE STOREFRONT DOOR AND WINDOW PRODUCT APPROVALS. FBC
 107.2.1
  