Plan Review Notes
Plan Review Notes For Permit 20050374
Permit Number 20050374
Review Stop G
Sequence Number 1
Notes
Date Text
2020-05-27 12:42:381ST REVIEW FBC-2017 RES. GAS
 PERMIT- 20050374
 5/27/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A COMPLETE REVIEW OF THE GAS PIPING CANNOT BE
 ACCOMPLISHED WITHOUT SUBMITTAL OF MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION GUIDELINES FOR ALL OF
 THE GAS-FIRED APPLIANCES AND EQUIPMENT ON THE DRAWINGS-
 GENERATOR, TANKLESS WATER HEATERS, COOKTOP, FIREPLACE,
 AND PRESSURE REGULATORS- SECTION 2408.1 FBC RES. PLEASE
 NOTE THE FOLLOWING:
 A) SEPARATE PERMITS WILL BE REQUIRED FOR THE GENERATOR
 AND THE FUTURE BBQ- SECTION 107.2.1 WPB.
 B) THE PLAN SHOWS POOL EQUIPMENT. PLEASE CLARIFY IF
 THERE IS A GAS-FIRED POOL HEATER EXISTING OR TO BE
 INSTALLED, AND LABEL IT ACCORDINGLY ON THE PLAN. PLEASE
 NOTE THAT THE GAS LOAD OF THE HEATER WHETHER EXISTING
 OR PROPOSED SHALL BE ADDED INTO THE TOTAL LOAD OF THE
 SYSTEM- SECTION G2412.4 FBC RES.
  
 2) GAS ISOMETRIC:
 A) INDICATE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM
 FROM THE METER TO THE MOST REMOTE OUTLET- SECTIONS
 G2413.4.1 & G2413.4.2 FBC RES.
 B) SHOW THE LOCATIONS OF ALL REGULATORS AND INDICATE
 THE STEP-DOWN PRESSURES AT EACH LOCATION-SECTION
 G2413.2 & G2413.4.3 PLEASE NOTE THAT WHERE CONNECTED TO
 RIGID PIPING, A UNION SHALL BE INSTALLED WITHIN 1 FT.
 OF EITHER SIDE OF THE MP REGULATOR- SECTION G2421.2(7).
  
 3) IT APPEARS THAT THE TANKLESS WATER HEATERS WILL BE
 INSTALLED ON THE EXTERIOR WALLS OF THE BUILDINGS.
 PLEASE CONFIRM AND PROVIDE ELEVATION DRAWINGS SHOWING
 THE LOCATIONS OF THE UNITS ON THE EXTERIOR WALL WITH
 CLEARANCE DISTANCES SHOWN FROM GRADE, THE EAVES OR
 SOFFIT ABOVE, AND TO AIR INTAKES AND OPERABLE OPENINGS
 INTO THE BUILDING- SECTION G2408.1 FBC RES AND SECTION
 107.2.1 WPB. IF APPLICABLE TO THE INSTALLATION, PROVIDE
 A VENT FLUE DIAGRAM INDICATING THE TYPE AND SIZE OF THE
 VENT, LENGTH OF THE VENT RUN, TERMINATION POINT, HEIGHT
 ABOVE THE ROOF AND ANCHORING DETAILS- SECTIONS G2426
 THROUGH G2439 FBC- RES.
  
 4) THE TOTAL VALUE OF THE PROJECT SHALL INCLUDE THE
 COST OF THE GAS PIPING AND ALL APPLIANCES AND EQUIPMENT
 TO BE INSTALLED UNDER THIS PERMIT EXCLUDING THE
 GENERATOR, AND ANY APPLIANCES AND EQUIPMENT THAT WERE
 INCLUDED IN THE COST OF THE MAIN PERMIT- 19070954.
 PLEASE PROVIDE AN ITEMIZED COST BREAKDOWN- SECTION
 109.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  