2020-05-26 13:40:20 | REVIEWED BY JERRY SMITH. |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| NFPA 54 = NATIONAL FUEL GAS CODE |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 20050340 7500 MONTE VERDE LN |
| |
| 1ST REVIEW |
| |
| GAS COMMENTS: DENIED |
| |
| A REVIEW OF CITY RECORDS FAILED TO SHOW ANY PERMITTED |
| GAS WORK FOR THE EXISTING GENERATOR AT THIS ADDRESS. |
| PER WPB FBC SECTION 105, THE PERMIT APPLICATION SHALL |
| INCLUDE THE EXISTING SYSTEM IN ITS? ENTIRETY. A GAS |
| PLAN PROVIDING COMPLETE PLANS, APPLIANCE/ EQUIPMENT |
| SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE |
| SCOPE OF EXISTING GAS WORK AS WELL AS THE UNDERGROUND |
| TANK REPLACEMENT. PER WPB FBC 110.2.1, A TEST OF THE |
| EXISTING SYSTEM SHALL BE REQUIRED PRIOR TO ISSUANCE OF |
| PERMIT; EXISTING WORK WHICH IS CONCEALED MAY BE |
| REQUIRED TO BE EXPOSED. CALL 561-805-6692 FOR FURTHER |
| INFORMATION. PER WPB FBC 109.4, APPLICATION IS SUBJECT |
| TO PENALTY FEES IN ADDITION TO THE REGULAR PERMIT FEES. |
| |
| A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS |
| FROM THE FIRST REVIEW. |
| |
| RANGE REQUIRES 120 VOLT POWER. AN ELECTRICAL PERMIT MAY |
| BE REQUIRED. |
| |
| PLEASE NOTE THE FOLLOWING ADDITIONAL COMMENTS: |
| 1. PER WPB FBC 107.2.1, IF USING COPPER, PROVIDE AN |
| AFFIDAVIT THAT THE GAS BEING CONVEYED DOES NOT CONTAIN |
| MORE THAN AN AVERAGE OF 0.3 GRAINS OF HYDROGEN SULFIDE |
| PER 100 STANDARD CU. FT. OF GAS TO SHOW COMPLIANCE WITH |
| FBC FG 403.4.3. |
| 2. PER WPB FBC 107.2.1, SPECIFY COPPER TYPE AS TYPE ACR |
| OR TYPE K & L |
| 3. PER WPB FBC 107.2.1, CLEARLY INDICATE ON THE PLANS |
| THE SIZES, DISTANCES AND MATERIAL OF THE EXISTING 2 PSI |
| PIPING AS NOTED ON THE REDLINED RISER DIAGRAM. PLEASE |
| NOTE, THE NEW EXTENSION OF THE 2 PSI SYSTEM SHALL BE |
| SIZED BASED UPON THE LONGEST RUN FROM THE METER TO THE |
| FARTHEST MP REGULATOR WHICH MAY VERY WELL BE AT THE |
| EXISTING GENERATOR. THAT DISTANCE SHALL BE NOTED IN THE |
| CALCULATIONS. |
| 4. PER WPB FBC 107.2.1, SUBMIT CALCULATIONS FOR |
| COMBUSTION AIR FOR THE RANGE PER FBC FG 304.1 |
| 5. PER WPB FBC 107.2.1, SHOW LOCATIONS OF EXISTING |
| APPLIANCES ON KEY PLAN. |
| 6. PER WPB FBC 107.2.1, CLEARLY IDENTIFY ALL MP |
| REGULATORS. |
| 7. REGARDING NEW LOW PRESSURE PIPING TO THE NEW |
| APPLIANCES, 183,000 BTU DEMAND EXCEEDS THAT ALLOWED FOR |
| ? INCH SIZE FROM MP REGULATOR TO THE TEE AND ? INCH |
| SIZE BRANCH TO RANGE BY TABLE FBC FG 402.4(9). I SEE IN |
| EXCESS OF 40 FEET FROM MP REGULATOR TO THE FURTHEST |
| APPLIANCE. THAT LONGEST LENGTH IN THIS SYSTEM SHALL BE |
| INDICATED IN THE CALCULATIONS. THE REGULATOR AND PIPING |
| FROM THE REGULATOR SHALL BE SIZED TO SUPPORT 183,000 |
| BTUS. THE BRANCH TO THE RANGE SHALL BE SIZED TO SUPPORT |
| 108,000 BTUS AND THE RUN FROM THAT BRANCH CONNECTION TO |
| THE GRILL SHALL BE SIZED TO SUPPORT 75,000 BTUS. |
| 8. PLEASE REVIEW REDLINED COMMENTS ON GAS RISER FOR |
| MORE CLARIFICATION. |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS |
| REQUIRED BY FAC AND FS. |
| ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-246-0882 MOBILE |
| |
| 20050340 7500 MONTE VERDE LN |
| |
| |
| |
| |
| |
| |
| |