2020-06-05 13:21:09 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| PART VIII ELECTRICAL |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| FLORIDA BUILDING CODE 2017 6TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| NFPA 70 2014 EDITION |
| |
| JAKE LEAHY BN, BU, PX |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| |
| 1) LOAD CALCULATION REQUIRED FOR 200A PANEL, LOAD |
| CALCULATION ON STORAGE PANEL WHAT SECTION OF THE CODE |
| DOES IT COME FROM? |
| |
| PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING |
| AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS |
| ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3 |
| |
| 2) GROUNDING ELECTRODE SYSTEM REQUIRED AT SEPARATE |
| BUILDING. |
| |
| A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE |
| ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND |
| CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF |
| GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC |
| RE3607.3 |
| |
| 3) WHAT SIZE BREAKER IS FEEDING THE STORAGE UNIT? 215.5 |
| |
| 4) TANKLESS WATER HEATER AT 5700W CAN NOT BE INSTALLED |
| ON A 60A BREAKER. |
| |
| 5) AHU 2500W ON EACH PHASE OR 1250 ON EACH PHASE? |
| |
| 6) STORAGE PANEL HAS MORE THAN 6 THROWS OF THE HAND TO |
| SHUT OFF A MAIN BREAKER IS NEEDED, |
| |
| 225.33 MAXIMUM NUMBER OF DISCONNECTS (A) GENERAL. TH E |
| DISCONNECTING MEANS FOR EACH SUPPLY PERMITTED BY 225.30 |
| SHALL CONSIST OF NOT MORE THAN SIX SWITCHES OR SIX |
| CIRCUIT BREAKERS MOUNTED IN A SINGLE ENCLOSURE, IN A |
| GROUP OF SEPARATE ENCLOSURES, OR IN OR ON A SWITCHBOARD |
| OR SWITCHGEAR. THERE SHALL BE NO MORE THAN SIX |
| DISCONNECTS PER SUPPLY GROUPED IN ANY ONE LOCATION |