2021-02-04 11:18:321ST REVIEW FBC-2020 MECHANICAL
 PERMIT-20050306
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW THE GENERATOR INSIDE THE GENERATOR ROOM,
 PLEASE SHOW THE EXHAUST FROM THE GENERATOR AND THE WALL
 IT IS EXHAUSTING OUT OF. FBC 107.2.1
  
 2) PLEASE PROVIDE A DETAILED DRAWING SHOWING THE FUEL
 PIPING SYSTEM INCLUDING FROM TANK TO GENERATOR. ALSO
 SHOW THE FILL PIPING LOCATION ALONG WITH THE VENT
 PIPING AND TERMINATION LOCATION. FBC M 1305.6, 1305.7
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  