2021-02-04 11:18:32 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-20050306 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2020 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2020 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE SHOW THE GENERATOR INSIDE THE GENERATOR ROOM, |
| PLEASE SHOW THE EXHAUST FROM THE GENERATOR AND THE WALL |
| IT IS EXHAUSTING OUT OF. FBC 107.2.1 |
| |
| 2) PLEASE PROVIDE A DETAILED DRAWING SHOWING THE FUEL |
| PIPING SYSTEM INCLUDING FROM TANK TO GENERATOR. ALSO |
| SHOW THE FILL PIPING LOCATION ALONG WITH THE VENT |
| PIPING AND TERMINATION LOCATION. FBC M 1305.6, 1305.7 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |