Plan Review Notes For Permit 20050284 |
Permit Number |
20050284 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-05-13 10:42:13 | SHUTTERS | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | | 1. FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION | | OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL | | INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL | | SPREADSHEET): | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS?PAGE=2 | | | | 2. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE | | NOTE PAGE 13 OF 20, FACTORS APPLY DEPENDING ON | | SUBSTRATE, EDGE DISTANCE AND FASTENER. FOR FASTENER, IF | | USING TAPCON, BE SPECIFIC AS TO WHICH TAPCON (TAPCON | | W/ADVANCED THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR). | | |
|