Date |
Text |
2020-06-10 16:43:23 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20050267 |
| |
| CODES IN EFFECT: |
| |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE SPECS FOR THE TYPE OF PIPING USED. |
| FBC FS 107.2.1 |
| |
| 2) PLEASE PROVIDE MODEL NUMBER AND SPECS FOR REGULATOR |
| USED. FBC FS 107.2.1 |
| |
| 3) PLEASE PROVIDE GAS TABLE USED FOR SIZING THE 10 PSI |
| PE GAS LINE. FBC FS 107.2.1 |
| |
| 4) PLEASE PROVIDE THE SPEC SHEETS FOR THE FLEXIBLE GAS |
| LINE HOSE USED TO CONNECT THE GENERATOR. FBC FS 107.2.1 |
| |
| 5) PLEASE SHOW THAT THE GENERATOR IS COMPLYING WITH |
| THE MANUFACTURER CLEARANCES FROM OPENABLE OPENINGS TO |
| THE STRUCTURE. FBC FS 107.2.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |
| MICHAEL EDWARDS |
| MECHANICAL EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL. 33401 |
| 561-805-6728 |
| [email protected] |
| |