Plan Review Notes
Plan Review Notes For Permit 20050265
Permit Number 20050265
Review Stop B
Sequence Number 2
Notes
Date Text
2020-08-03 13:22:28PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PREFAB GENERATOR PAD ENGINEERING THAT WAS
 SUBMITTED HAS A REQUIRED MINIMUM WEIGHT OF 466 LBS. FOR
 THE 22KW GENERATOR. THE 22 KW GENERATOR IN THE
 SPECIFICATIONS THAT WERE SUBMITTED HAS A WEIGHT OF 445
 LBS. THE 445 LBS. GENERATOR DOES NOT MEET THE WEIGHT
 REQUIRED BY THE PAD ENGINEERING. FBC 107
  
 2) SEE SIGNATURE REVIEW NOTES.