Plan Review Notes For Permit 20050265 |
Permit Number |
20050265 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-08-03 13:22:28 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE PREFAB GENERATOR PAD ENGINEERING THAT WAS | | SUBMITTED HAS A REQUIRED MINIMUM WEIGHT OF 466 LBS. FOR | | THE 22KW GENERATOR. THE 22 KW GENERATOR IN THE | | SPECIFICATIONS THAT WERE SUBMITTED HAS A WEIGHT OF 445 | | LBS. THE 445 LBS. GENERATOR DOES NOT MEET THE WEIGHT | | REQUIRED BY THE PAD ENGINEERING. FBC 107 | | | | 2) SEE SIGNATURE REVIEW NOTES. |
|