Plan Review Notes
Plan Review Notes For Permit 20050249
Permit Number 20050249
Review Stop G
Sequence Number 1
Notes
Date Text
2020-06-04 11:34:54I COULD NOT DO THIS REVIEW: REVISED SPEC SHEETS FOR THE
 APPLIANCES DID NOT UPLOAD, THEY ARE BLANK PAGES. PLEASE
 RESUBMIT THE REVISED SPEC SHEETS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
2020-05-26 08:36:091ST REVIEW FBC-2017 MECHANICAL
 PERMIT- 20050249
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE SPECIFICATIONS FOR THE GENERATOR (
 INCLUDE THE MODEL #). FBC FS 107.2.1
  
 2) PLEASE PROVIDE THE MODEL #?S FOR THE POOL HEATER,
 THE GAS FIREPLACE, AND THE WATER HEATER. FBC FS 107.2.1
  
 3) PLEASE SHOW THE MATERIAL USED FOR THIS UNDERGROUND
 GAS SYSTEM INSIDE THE STRUCTURE MEETS- FBC FG 404.17
  
 4) IS THIS SYSTEM RUNNING UNDERGROUND INSIDE THE
 STRUCTURE? IF SO, PLEASE SHOW HOW THIS SYSTEM MEETS-
 FBC FG 404.6 AND FBC FG 404.8
  
 5) PLEASE PROVIDE A LEGIBLE GAS LINE DIAGRAM SHOWING
 EACH MP REGULATOR AT THE APPLIANCES AND TYPE OF
 MATERIAL USED IN THE ENTIRE SYSTEM . FBC FS 107.2.1
  
 6) PLEASE PROVIDE THE PRESSURE DROP FOR THIS SYSTEM.
 FBC FS 107.2.1
  
 7) PLEASE SHOW ACCESS PROVIDED FOR EACH MP REGULATOR AT
 THE APPLIANCES. FBC FG 410.1 AND FBC FG 410.2
  
  
 8) THE MANUAL FOR THE GAS RANGE INDICATES A TOTAL OF
 6-BURNERS AND 1 GRIDDLE. WITH A COMBINED TOTAL OF
 110,000 BTU?S. THE DRAWING PRESENTED IN THIS PACKAGE IS
 INDICATING ONLY 77,200 BTU?S FOR THIS RANGE. PLEASE
 CORRECT THE BTU?S. FBC FS 107.2.1
  
 9) PLEASE PROVIDE THE TABLE NUMBERS USED TO SIZE THIS
 GAS PIPING SYSTEM. FBC FS 1.07.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  