Plan Review Notes For Permit 20050225 |
Permit Number |
20050225 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-05-14 10:22:59 | ROOFING | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE FLAT | | DECK ROOFING. (PLEASE CIRCLE THE ROOFING SYSTEM TO BE | | USED IN THE FLAT DECK PRODUCT APPROVAL) | | 2) ROOFING SYSTEM TO BE USED ON THE FLAT DECK MAY | | REQUIRE ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS | | FROM AN ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND | | 3 WHICH REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM | | SHOWN ON THE PRODUCT APPROVAL - SEE NOTES ON THE | | PRODUCT APPROVAL. SIGNED AND SEALED DRAWINGS OR | | DOCUMENTS WILL NEED TO BE DIGITALLY SIGNED AND SEALED | | TO BE USED IN ELECTRONIC PLAN REVIEW. |
|