2020-05-14 10:22:59ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE FLAT
 DECK ROOFING. (PLEASE CIRCLE THE ROOFING SYSTEM TO BE
 USED IN THE FLAT DECK PRODUCT APPROVAL)
 2) ROOFING SYSTEM TO BE USED ON THE FLAT DECK MAY
 REQUIRE ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS
 FROM AN ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND
 3 WHICH REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM
 SHOWN ON THE PRODUCT APPROVAL - SEE NOTES ON THE
 PRODUCT APPROVAL. SIGNED AND SEALED DRAWINGS OR
 DOCUMENTS WILL NEED TO BE DIGITALLY SIGNED AND SEALED
 TO BE USED IN ELECTRONIC PLAN REVIEW.