2020-07-21 07:56:58GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) THE REVISED GENERATOR PAD DRAWING HAS A LIST OF
 GENERATORS AND THEIR WIND DESIGN VALUES - IT DOES NOT
 LIST ANY OF THE GENERATOR MODEL NUMBERS ON THE
 GENERATOR SPEC. SHEET PROVIDED - SO THE WIND DESIGN
 PRESSURES ARE STILL UNKNOWN. PLEASE PROVIDE SIGNED AND
 SEALED GENERATOR SLAB AND TIEDOWN DETAILS FROM AN
 ARCHITECT OR ENGINEER TO COMPLY WITH THE WIND LOADS FBC
 1609
  
 FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO
 BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG
 WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON
 FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM. (AT THIS TIME DROP BOX ITEMS
 MAY TAKE 2 TO 3 WEEKS TO PROCESS, TO SEND TO PLAN
 REVIEW - DUE TO LIMITED STAFF INSIDE THE BUILDING
 DEPT.)
  