2020-05-27 16:43:38GENERATOR PAD
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) NEED SIGNED AND SEALED SITE SPECIFIC WIND DESIGN
 PRESSURES FROM AN ARCHITECT OR ENGINEER TO VERIFY WITH
 THE ALLOWABLE WIND PRESSURES SHOWN ON THE PAD
 ENGINEERING (SEE NOTE NUMBER 2 ON THE PROVIDED PAD
 ENGINEERING).
 2) ALL SIGNED AND SEALED ENGINEERING NEEDS TO BE
 DIGITALLY SIGNED AND SEALED BY THE ENGINEER.
  