Plan Review Notes
Plan Review Notes For Permit 20050210
Permit Number 20050210
Review Stop G
Sequence Number 1
Notes
Date Text
2020-05-18 08:18:221) SHOW THE LOCATION OF ALL THE REGULATORS ON THE GAS
 DRAWING.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GAS
 REGULATORS. RREGULATORS INSTALLED ON THE EXTERIOR OF
 BUILDINGS SHALL BE APPROVED FOR OUTDOOR INSTALLATION.
 FBC-FUEL GAS SEC.410.1.
 3 ) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 4) SHOW THE DISTANCE FROM EACH REGULATOR TO THE
 APPLIANCE AND SIZE EACH LINE FROM THE REGULATOR TO THE
 APPLIANCE.
 5) SUBMIT A FLOOR PLAN THAT SHOWS THE DISTANCE OF THE
 TANKLESS WATER HEATERS TO ALL OPERABLE DOORS, WINDOWS
 AND OTHER BUILDING OPENINGS. THE LOCATION OF THE
 TANKLESS WATER HEATERS SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION MANUAL.
 6) NOTE ON THE GAS RISER WHAT SIZING TABLES ARE BEING
 USED FOR THE DESIGN OF THE LOW PRESSURE SYSTEM FOR THE
 CSST AND SCH. 40 PIPE.
  
 NOTE: ACCORDING TO CITY RECORDS, A GAS PLAN REVIEW WAS
 NEVER DONE ON THE MASTER PERMIT AS THERE WAS NO GAS
 DRAWING SUBMITTED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW