Plan Review Notes For Permit 20050173 |
Permit Number |
20050173 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-06-25 09:59:10 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. FIRE ALARM SHEETS SHOULD BE REMOVED FROM THIS | | SUBMITTAL AND SUBMITTED AS A REVISION TO THE FIRE ALARM | | PERMIT. PROVIDE CORRECTION. WPB FBC 105.1, 107.2.1 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|