Plan Review Notes For Permit 20050173 |
Permit Number |
20050173 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-05-21 10:58:28 | 1ST REVIEW FBC-2017 PLUMBING | | PERMIT 20050173 | | 5/21/20 | | | | CODES IN EFFECT: | | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) REVISE SHEET P-5.14 (PARKING GARAGE STORM DRAINAGE | | ISOMETRIC) TO SHOW THE PROPSED CHANGES TO THE STORM | | WATER RISER IN THE PARKING GARAGE- SECTION 107.2.1 WPB. | | | | 2) PLUMBING PLANS NOT SIGNED AND SEALED BY THE | | ENGINEER- SEE COMMENTS UNDER SIGNATURE REVIEW- SECTION | | 107.2.1 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | | | |
|