Plan Review Notes
Plan Review Notes For Permit 20050034
Permit Number 20050034
Review Stop P
Sequence Number 2
Notes
Date Text
2020-07-14 15:48:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20050034 600 @ CLEMATIS ST
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
  
 ORIGINAL COMMENT #1
 1. PLAN SHEET L2.03 INDICATES AN EXISTING CONTROLLER
 FOR THE SYSTEM. PLAN SHEET L2.12 SECTION 2.14 APPEARS
 TO REQUIRE A NEW CONTROLLER WITH SPECIFIC REQUIREMENTS.
 PER WPB FBC 107.2.1, CLARIFY.
  
 RESPONSE
 PER THE AS BUILT PLANS PROVIDED BY THE CITY, VALVES FOR
 THIS BLOCK WILL USE EXISTING METER, CONTROLLER AND RAIN
 SENSOR (DISCUSS ASBUILT SCHEDULE L2.00)
 ORIGINAL COMMENT #2
  
  
 2. PER WPB FBC 107.2.1, PROVIDE LOCATION OF THE
 REQUIRED RAIN SENSOR AND NOTE EXISTING OR NEW.
  
 RESPONSE
 EXISTING CONTROLLER AND RAIN SENSOR LOCATED AT THE
 POLICE STATION (BEHIND DUMPSTER ENCLOSURE, OFF BANYAN
 BLVD.) TO BE USED FOR THIS BLOCK.
  
  
 NEW COMMENT
 PER WPB FBC 107.2.1, PROVIDE ON THE PLAN AT WHAT
 APPEARS TO BE THE SERVICE CONNECTION A NOTE STATING
 THAT
 1. EXISTING CONTROLLER AND RAIN SENSOR LOCATED AT THE
 POLICE STATION (BEHIND DUMPSTER ENCLOSURE, OFF BANYAN
 BLVD.) TO BE USED FOR THIS BLOCK.
 2. CONNECT TO EXISTING METER, CONTROLLER AND BACKFLOW
 PREVENTOR
  
 PROVISO: A FIELD INSPECTOR'S APPROVAL WHICH WILL
 INCLUDE FIELD REVIEW OF EXISTING BACKFLOW PREVENTER,
 CONTROLLER AND RAIN SENSOR FOR COMPLIANCE WILL BE
 REQUIRED AT TIME OF INSPECTION
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  