2020-07-14 15:04:52 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 20050033 500 @ CLEMATIS ST |
| |
| 2ND REVIEW |
| PLUMBING COMMENTS: DENIED |
| |
| ORIGINAL COMMENT: |
| 1. PLAN SHEET L2.03 INDICATES AN EXISTING CONTROLLER |
| FOR THE SYSTEM. PLAN SHEET L2.12 SECTION 2.14 APPEARS |
| TO REQUIRE A NEW CONTROLLER WITH SPECIFIC REQUIREMENTS. |
| PER WPB FBC 107.2.1, CLARIFY. |
| |
| RESPONSE: |
| A NEW METER, BACKFLOW PREVENTOR AND CONTROLLER HAVE |
| BEEN SPECIFIED FOR THIS BLOCK. SEE L2.03 FOR LOCATION. |
| |
| NEW COMMENTS: |
| 1. PLAN SHEET L2.03 ONLY INDICATES EXISTING METER |
| BACKFLOW PREVENTOR AND CONTROLLER TO BE ABANDONED. |
| THERE IS NO INDICATION OF ANY NEW METER, BACKFLOW |
| PREVENTOR AND CONTROLLER ON ANY PLAN SHEET FOR 500 |
| BLOCK. ADDITIONALLY I SEE NO CONNECTION POINT FOR |
| SERVICE TO THE SYSTEM. PER WPB FBC 107.2.1, PROVIDE ON |
| PLANS THE LOCATION OF THE NEW METER, BACKFLOW PREVENTOR |
| AND CONTROLLER, AS WELL AS A RAIN SENSOR W/ MOUNTING |
| LOCATION AND MOUNTING DETAIL FOR 500 BLOCK. |
| |
| 2. PER WPB FBC 107.2.1, PROVIDE LOCATION OF THE |
| REQUIRED RAIN SENSOR AND NOTE EXISTING OR NEW. |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| |
| |
| |