2020-06-16 12:18:02 | REVIEWED BY JERRY SMITH. |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 20050033 500 @ CLEMATIS ST |
| |
| PER WPB FBC 107.3.5.1.2(6), A SEPARATE ELECTRICAL |
| PERMIT IS REQUIRED FOR THE LOW VOLTAGE |
| |
| 1ST REVIEW |
| PLUMBING COMMENTS: |
| |
| 1. PLAN SHEET L2.03 INDICATES AN EXISTING CONTROLLER |
| FOR THE SYSTEM. PLAN SHEET L2.12 SECTION 2.14 APPEARS |
| TO REQUIRE A NEW CONTROLLER WITH SPECIFIC REQUIREMENTS. |
| PER WPB FBC 107.2.1, CLARIFY. |
| 2. PER WPB FBC 107.2.1, PROVIDE LOCATION OF THE |
| REQUIRED RAIN SENSOR AND NOTE EXISTING OR NEW. |
| |
| PROVISO: |
| A FIELD INSPECTOR'S APPROVAL WHICH WILL INCLUDE FIELD |
| REVIEW OF EXISTING BACKFLOW PREVENTER, CONTROLLER AND |
| RAIN SENSOR FOR COMPLIANCE WILL BE REQUIRED AT TIME OF |
| INSPECTION |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS |
| REQUIRED BY FAC AND FS. |
| ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| |
| |
| |