2020-06-15 12:16:591) SHOW ALL THE NEW AND RELOCATED PLUMBING FIXTURES ON
 THE WATER RISER. WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 2) THE TOILET ROOM DOOR APPEARS TO SWING INTO THE CLEAR
 FLOOR SPACE FOR THE DRINKING FOUNTAIN. DOORS SHALL NOT
 SWING INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED
 FOR ANY FIXTURE PER 2017 FBC-ACCESS. SEC.602.2.3.
 3) SHT. MP.1 - NEW BATH SANITARY RISER - THE WASHING
 MACHINE CANNOT DISCHARGE INTO A HORIZONTAL WET VENT PER
 FBC-PLUMBING SEC.912.1. THE WASHING MACHINE SHALL
 CONNECT TO THE HORIZONTAL DRAIN DOWNSTREAM OF THE WATER
 CLOSET.
 4) SHT.MP-1 - 1ST FLOOR BATH SANITARY RISER - THE
 DRINKING FOUNTAIN AND THE SINK CANNOT DISCHARGE INTO A
 HORIZONTAL WET VENT PER 2017 FBC-PLUMBING SEC.
 912.1.THE DRINKING FOUNTAIN AND FUTURE SINK SHALL
 CONNECT TO THE HORIZONTAL DRAIN DOWNSTRAM OF THE STACK
 TO THE 2ND FLOOR.
 5) IN ORDER TO UTILIZE AN AIR ADMITTANCE VALVE THERE
 MUST BE A MINIMUM OF ONE STACK VENT OR VENT STACK
 EXTENDED TO THE OUTDOORS TO THE OPEN AIR PER
 FBC-PLUMBING SEC.918.7. SHOW COMPLIANCE ON THE PLANS.
 6) SUBMIT A DETAIL OF THE DRYWELL FOR THE CONDENSATE
 LINE.
 7) SHOW THE SHOWER DIMENSIONS ON THE PLANS. COMPLY WITH
 FBC-PLUMBING SEC. 417.4.
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 TANKLESS WATER HEATERS. WPB AMEND. TO FBC SEC. 107.2.1.
 9) SHOW BOTH TANKLESS WATER HEATERS ON THE WATER RISER
 ALONG WITH ALL CONNECTED FIXTURES. WPB AMEND. TO FBC
 SEC. 107.2.1.
 10) THE SANITARY RISER SHOWS A 1 INCH DRAIN FOR THE
 DRINKING FOUNTAIN. CLARIFY.
 11) SHT. A.1 - TOILET ACCESSORY SCHEDULE AND ELEVATIONS
 - THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE PER FBC-ACCESS. SEC.609.4.
 12) SHT. A.1 - THERE IS A NOTE BY THE GRAB BAR
 INSTALLATION DETAIL THAT REFERENCES THE 2010 FBC.
 DELETE THIS NOTE.
 13) SHT. A.1 - TYPICAL TOILET ROOM PLAN SHOWS THE
 CCLEAR FLOOR SPACE FOR THE WATER CLOSETAS 56 INCHES
 WIDE BY 60 INCHES DEEP.THE CLEAR FLOOR SPACE SHALL BE
 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM
 THE REAR WALL PER FBC-ACCESS. SEC.604.3.1.
 14) THE TOILET PAPER HOLDER SHALL BE LOCATED IN
 ACCORDANCE WITH FBC-ACCESS. SEC.604.7. SHOW THE
 DIMENSIONS ON THE PLANS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH BUILDING DIVISION
 401 CLEMATIS ST.
 P.O. BOX 3147
 WEST PALM BEACH, FL.33402
 [email protected]
 P: 561-805-6692
 F: 561-805-6676
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved