Plan Review Notes
Plan Review Notes For Permit 20041170
Permit Number 20041170
Review Stop B
Sequence Number 1
Notes
Date Text
2020-05-17 12:28:032017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20041170
 ADD: 6821 NORTON AVE.
 CONT: COASTAL WINDOWS & DOORS
 TEL: 561-842-7000
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUNDAY MAY 17, 2020
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION UNDER THE DESCRIPTION OF WORK
 INDICATES REMODELING IN THE FIRST FLOOR OCCUPANCY,
 WHEREAS THE COVERSHEET C-1 UNDER THE SCOPE OF WORK NOTE
 # 1 REMODEL OF THE 1ST FL. AND RESTROOM & NOTE 2
 INDICATES THE REMODEL OF THE 2ND FLOOR. THERE IS A
 DISCREPANCY BETWEEN THE PERMIT APPLICATION AND THE 2ND
 FLOOR. 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED,
 DISCREPANCY IN THE DESCRIPTION OF WORK TO BE
 ACCOMPLISHED UNDER THIS PERMIT.
  
 2) SHEET A-1:
  
 2A) THE PLANS SHEET A-1 INDICATE UNDER THE HEADING
 PROJECT DATA THE OCCUPANCY TYPE IS A-3 BUT THE OCCUPANT
 LOAD IS TAKEN AS A BUSINESS OCCUPANCY 1350 SQ. FT. /
 100 SQ. FT. (OCCUPANT LOAD FACTOR/ TABLE 1004.1.2.).
 PLEASE REVIEW TABLE 11004.1.2 EXHIBIT GALLERIES (A-3)
 OCCUPANT LOAD FACTOR IS TO BE TAKEN AT 30 NET. PLEASE
 UPDATE THE OCCUPANT LOAD (NET).
 2017 FBC-B 201: FLOOR AREA, NET. THE ACTUAL OCCUPIED
 AREA NOT INCLUDING UNOCCUPIED ACCESSORY AREAS SUCH AS
 CORRIDORS, STAIRWAYS, TOILET ROOMS, MECHANICAL ROOMS
 AND CLOSETS.
  
 2B) THE PLANS SHEET A-1 INDICATE UNDER THE HEADING
 PROJECT DATA THE OCCUPANCY TYPE IS A-3 BUT IF UNDER
 COMMENT # 1 THE WORK TO BE ACCOMPLISHED UNDER THIS
 PERMIT IS THE REMODEL OF BOTH THE 1ST & 2ND FLOOR THEN
 THIS SHOULD BE CONSIDERED A MIXED USE OCCUPANCY, 1ST
 FLOOR A-3 AND THE 2ND FLOOR R-3. SEE THE 2017 FBC-B
 SECTION 508.1 & TABLE 707.3.10.
  
 2C) THE PLAN SHEET A-1 INDICATES UNDER THE HEADING
 PROJECT DATA THE PLAN IS SILENT TO THE 2ND FLOOR
 OCCUPANCY WHERE THE 2ND FLOOR PLAN DOES INDICATE WORK
 TO BE ACCOMPLISHED IN THIS SET OF PLAN DOCUMENTS, NOTES
 3, 4 & 5. THE PROJECT DATA DOES NOT INDICATE THE TYPE
 OF OCCUPANCY THE 2ND FLOOR HOUSES NOR THE PROPOSED
 OCCUPANT LOAD. SEE 2017 FBC-B SECTIONS 310.5 & TABLE
 1004.1.2.
  
 2D) SHEET A-1 SHOWS ONLY ONE MEANS OF EGRESS TO THE 2ND
 STORY R-3 RESIDENCE, AN EXTERIOR STAIR. SHEET A-1 ALSO
 HAS A NOTE ABOUT A NEW STOREFRONT IN THE FORMER
 OVERHEAD DOOR OPENING. THERE ARE NO ELEVATION DRAWINGS
 OF THIS SIDE VIEW BUT THE PLANS FAIL TO SHOW COMPLIANCE
 WITH SECTION 1027.6 EXTERIOR EXIT STAIRWAY PROTECTION.
 YOU CAN ALSO SEE THE 2015 IBC CODE COMMENTARY FIGURE
 1027.6(1) WHERE WITHIN THE VERTICAL CROSSED HATCHED
 LINES NO OPENINGS EXCEPT FOR 1 HOUR RATED DOORS AND
 OPENINGS OUTSIDE OF THE STAIR AND LANDINGS BUT WITHIN
 10 FEET OF EITHER THE STAIR OR LANDING ? HOUR OPENING
 PROTECTIVES ARE REQUIRED. THIS WAS NOT ADDRESSED UNDER
 THE PERMIT 20031278.
  
 2E) SHEET A-1 GIVE THE WIND DESIGN CRITERIA BUT NOT THE
 PRESSURES FOR THE NEW EXTERIOR DOOR AND WINDOW OPENINGS
 FOR THE 1ST FLOOR AND 2ND FLOOR.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 2E)(1-3.) COMPLIED.
  
 2E)(4.) APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 2E)(5.) DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 2E)(6.) TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 3) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS,
  
 4) GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH
 IF UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2017 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 5A) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5B) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 6) SHEET A-1 TOILET ACCESSORY SCHEDULE:
 6A) BOTH GB & GB-1 BOTH STATE THE GRAB BAR IS TO BE
 INSTALLED @ 33 INCHES A.F.F. ?CENTERLINE OF GRAB BAR.
 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF
 GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 6B) TPH TOILET PAPER HOLDER INDICATES IT IS TO BE
 MOUNTED MIN. / MAX. 36 INCHES FROM THE REAR WALL.
 2017 ACCESSIBILITY CODE SECTION 604.7. TOILET PAPER
 DISPENSERS SHALL COMPLY WITH 309.4 AND SHALL BE 7-9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTER LINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED
 BEHIND THE GRAB BARS.
  
 7) THE FLOOR PLAN SHOWS A SINGLE WATER FOUNTAIN. PLEASE
 SHOW COMPLIANCE WITH 2017 FBC-ACCESSIBILITY CODE. 211.2
 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS
 SHALL BE PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.1 THROUGH 602.6 AND ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.7.
  
 8) THE 2ND FLOOR (A-1) PLAN STATES WITH NOTE 3 THAT A
 NEW DOORWAY TO THE ADDED FOR ACCESS TO THE ROOF DECK.
 THE PLANS DO NOT PROVIDE ANY STRUCTURAL SHEETS AND OR
 DETAILS HOW THIS WILL OCCUR. THE SHEET A-1 DOES NOT
 EVEN LET US KNOW IF THIS BUILDING IS CBS CONSTRUCTION
 OR WOOD FRAME. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 9) COMPLIED. 7/16/2020 TEL. MEETING ARCH. JIM PAINE
  
 10) THIS NOTE IS TO BE DISCUSSED WITH THE BUILDING
 OFFICIAL, THE SECOND FLOOR COMMON PATH OF TRAVEL FOR
 THE 2ND FLOOR IS TO THE MOST REMOTE POINT OF THE 2ND
 FLOOR TO THE EXIT DISCHARGE, THE BOTTOM OF THE STAIRS.
  
 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE
 TO CONTACT ME, MY CELL NUMBER IS 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  