2020-06-04 10:57:23 | 2ND REVIEW FBC-2017 FUEL GAS |
| PERMIT #20041156 |
| 6/4/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| COMMENTS FROM THE 1ST REVIEW STILL EXIST- NO CORRECTED |
| PALNS WERE SUBMITTED. |
| |
| 1) GAS ISOMETRIC: |
| A) INDICATED ON THE ISO ARE EXTERIOR AND INTERIOR RUN |
| LENGTHS. PLEASE INDICATE THE TOTAL DEVELOPED LENGTH OF |
| THE SYSTEM TO THE MOST REMOTE OUTLET. IT APPEARS THAT |
| THE VERTICAL LENGTH OF GALVANIZED PIPING BETWEEN THE |
| TWO CSST RUNS WAS NOT INCLUDED- SECTIONS G2413.4.1 & |
| G2413.4.2 FBC RES |
| B) INDICATE THE TOTAL BTUH LOAD OF THE SYSTEM-- SECTION |
| 2413.2. PLEASE NOTE THAT THE ISO INDICATES THE |
| GENERATOR TO BE 330,000 BTUH, BUT THERE IS ANOTHER |
| INCOMPLETE RISER DRAWING UPLOADED THAT INDICATES IT TO |
| BE 360.000 BTUH. |
| C) INDICATE THE GAS DELIVERY PRESSURE AT THE METER, AND |
| THE STEP-DOWN PRESSURES AT THE GENERATOR AND |
| APPLIANCES- SECTION G2413.2 & G2413.4.3 |
| D)) SHOW THE LOCATIONS OF ALL (MP) STEPDOWN REGULATORS |
| AND REQUIRED SHUT OFF VALVES. PLEASE NOTE THAT WHERE |
| CONNECTED TO RIGID PIPING, A UNION SHALL BE INSTALLED |
| WITHIN 1 FT. OF EITHER SIDE OF THE MP REGULATOR- |
| SECTION G2421.2(7). |
| E) LIST ALL PIPE SIZING TABLES USED FOR THE PE, |
| GALVANIZED, AND CSST PIPING- SEE TABLES G2413.4(1) |
| THROUGH G2413.4(21) FBC RES. |
| |
| 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW |
| GENERATOR- SECTION G2403.3 FBC RES. |
| |
| 3) PROVIDE A COPY OF A SURVEY OR SITE DRAWING SHOWING |
| THE LOCATION OF THE GENERATOR AND CLEARANCE DISTANCES |
| TO OPERABLE OPENINGS INTO THE BUILDING. PLEASE NOTE A |
| 10' CLEARANCE IS REQUIRED PER SECTION R303.5.1 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |