Plan Review Notes
Plan Review Notes For Permit 20041156
Permit Number 20041156
Review Stop G
Sequence Number 2
Notes
Date Text
2020-06-04 10:57:232ND REVIEW FBC-2017 FUEL GAS
 PERMIT #20041156
 6/4/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS FROM THE 1ST REVIEW STILL EXIST- NO CORRECTED
 PALNS WERE SUBMITTED.
  
 1) GAS ISOMETRIC:
 A) INDICATED ON THE ISO ARE EXTERIOR AND INTERIOR RUN
 LENGTHS. PLEASE INDICATE THE TOTAL DEVELOPED LENGTH OF
 THE SYSTEM TO THE MOST REMOTE OUTLET. IT APPEARS THAT
 THE VERTICAL LENGTH OF GALVANIZED PIPING BETWEEN THE
 TWO CSST RUNS WAS NOT INCLUDED- SECTIONS G2413.4.1 &
 G2413.4.2 FBC RES
 B) INDICATE THE TOTAL BTUH LOAD OF THE SYSTEM-- SECTION
 2413.2. PLEASE NOTE THAT THE ISO INDICATES THE
 GENERATOR TO BE 330,000 BTUH, BUT THERE IS ANOTHER
 INCOMPLETE RISER DRAWING UPLOADED THAT INDICATES IT TO
 BE 360.000 BTUH.
 C) INDICATE THE GAS DELIVERY PRESSURE AT THE METER, AND
 THE STEP-DOWN PRESSURES AT THE GENERATOR AND
 APPLIANCES- SECTION G2413.2 & G2413.4.3
 D)) SHOW THE LOCATIONS OF ALL (MP) STEPDOWN REGULATORS
 AND REQUIRED SHUT OFF VALVES. PLEASE NOTE THAT WHERE
 CONNECTED TO RIGID PIPING, A UNION SHALL BE INSTALLED
 WITHIN 1 FT. OF EITHER SIDE OF THE MP REGULATOR-
 SECTION G2421.2(7).
 E) LIST ALL PIPE SIZING TABLES USED FOR THE PE,
 GALVANIZED, AND CSST PIPING- SEE TABLES G2413.4(1)
 THROUGH G2413.4(21) FBC RES.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW
 GENERATOR- SECTION G2403.3 FBC RES.
  
 3) PROVIDE A COPY OF A SURVEY OR SITE DRAWING SHOWING
 THE LOCATION OF THE GENERATOR AND CLEARANCE DISTANCES
 TO OPERABLE OPENINGS INTO THE BUILDING. PLEASE NOTE A
 10' CLEARANCE IS REQUIRED PER SECTION R303.5.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  