Date |
Text |
2020-05-15 12:05:00 | |
| 1ST REVIEW FBC-2017 FUEL GAS |
| PERMIT #20041097 |
| 5/15/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) GAS ISOMETRIC: |
| A) THE 1/2" GALVANIZED PIPE SUPPLYING THE 72,000 BTUH |
| COOKTOP SHALL BE SIZED AT 3/4" PER TABLE G2413.4(1) FBC |
| RES. |
| B) INDICATE THE EHD'S (EQUIVALENT HYDRAULIC DIAMETERS) |
| OF THE CSST LINES- TABLE G2413.4(5). |
| |
| 2) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| INSTALLATION GUIDELINES FOR ALL GAS-FIRED APPLIANCES - |
| SECTION G2403.3 & G2408.1. |
| |
| 3) PROVIDE GAS VENTING PLANS FOR THE WATER HEATER, |
| FIREPLACE AND BBQ- SECTION G2425.1 |
| |
| 4) INDICATE HOW COMBUSTION WILL BE PROVIDED TO THE |
| INDOOR APPLIANCES AND EQUIPMENT. PLEASE INCLUDE |
| CALCULATIONS- SECTION G2407.1 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |
| |