Plan Review Notes
Plan Review Notes For Permit 20041097
Permit Number 20041097
Review Stop G
Sequence Number 1
Notes
Date Text
2020-05-15 12:05:00 
 1ST REVIEW FBC-2017 FUEL GAS
 PERMIT #20041097
 5/15/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS ISOMETRIC:
 A) THE 1/2" GALVANIZED PIPE SUPPLYING THE 72,000 BTUH
 COOKTOP SHALL BE SIZED AT 3/4" PER TABLE G2413.4(1) FBC
 RES.
 B) INDICATE THE EHD'S (EQUIVALENT HYDRAULIC DIAMETERS)
 OF THE CSST LINES- TABLE G2413.4(5).
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION GUIDELINES FOR ALL GAS-FIRED APPLIANCES -
 SECTION G2403.3 & G2408.1.
  
 3) PROVIDE GAS VENTING PLANS FOR THE WATER HEATER,
 FIREPLACE AND BBQ- SECTION G2425.1
  
 4) INDICATE HOW COMBUSTION WILL BE PROVIDED TO THE
 INDOOR APPLIANCES AND EQUIPMENT. PLEASE INCLUDE
 CALCULATIONS- SECTION G2407.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  