Plan Review Notes
Plan Review Notes For Permit 20041096
Permit Number 20041096
Review Stop G
Sequence Number 2
Notes
Date Text
2020-06-05 10:05:003RD REVIEW FBC-2017 MECHANICAL
 PERMIT-20041096
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE MODEL NUMBER OF THE REGULATOR
 USED AT EACH LOCATION IN THIS SYSTEM. FBC FS 107.2.1
  
 2) PLEASE PROVIDE SPECS. AND SHOW FLEXIBLE CONNECTOR
 USED TO CONNECT THE GENERATOR TO THE GAS LINE. FBC FS
 107.2.1
  
 3) THERE IS A MEASUREMENT OF 49? ON THE DRAWING, IS
 THIS THE LONGEST LENGTH TO THE MOST REMOTE APPLIANCE?
 IF NOT, WHY IS IT ON THE DRAWING? FBC FS 107.2.1
  
 4) PLEASE CLEAN THE DRAWING UP IN THE AREA OF THE
 METER, I CANNOT SEE ALL THE CONNECTIONS AND PIPE SIZES
 IN THIS AREA. FBC FS 107.2.1
  
 5) THERE IS A REFERENCE OF 3 TABLES USED TO SIZE THIS
 PIPING SYSTEM. TABLE 402.4(18) IS FOR CSST, I DO NOT
 SEE CSST ON THIS DRAWING. PLEASE SHOW ON THE DRAWING
 WHERE THE CSST IS TO BE USED IN THIS SYSTEM. FBC FS
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  