2020-05-14 13:51:34REVIEWED BY JERRY SMITH.
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20041096 140 MONROE DR
  
 GAS COMMENTS: DENIED
 1.SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE RANGE
 PER FBC FG 304.1
 2.SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM FBC FG 402.4.1, 402.4.2
 3.PER WPB FBC 107.2.1, SHOW PE TO GALVANIZED RIGID
 PIPING TRANSITION ON RISER DIAGRAM.
 4.PER WPB FBC 107.2.1, PROVIDE THE MATERIAL AND TABLE
 USED IN SIZING PIPING DOWNSTREAM OF MP REGULATOR(S).
 INDICATE ON THE PLAN THE DISTANCE FROM REGULATOR TO
 APPLIANCE.
 5.PER WPB FBC 107.2.1, PROVIDE DETAIL OF MP REGULATOR
 WITH SHUTOFF VALVE, UNION AND OTHER REQUIRED
 ACCESSORIES. COMPLY WITH FBC FG 410.2.
 6.PER WPB FBC 107.2.1, PROVIDE SITE W/BUILDING AND
 POOL/DIMENSIONED BUILDING PLAN VIEW DRAWING SHOWING
 BUILDING AND LAYOUT INCLUSIVE OF ROOMS, DOORS AND
 WINDOWS, LOCATIONS OF GAS APPLIANCES, PIPE ROUTING AND
 METER. INDICATE ON THE PLAN IF THE TANKLESS WATER
 HEATER IS REPLACING AN EXISTING TANKLESS WATER HEATER
 OR IS IT REPLACING A STORAGE TANK TYPE WATER HEATER OR
 IS IT BEING ADDED TO THE EXISTING HOT WATER SYSTEM?
 INDICATE ON THE APPLICATION IN THE DESCRIPTION OF WORK.
 IF REPLACING OR SUPPLEMENTING, IDENTIFY AND SHOW
 LOCATION OF THE EXISTING WATER HEATER. SHOW HORIZONTAL
 DISTANCE FROM ANY OUTSIDE APPLIANCE EXHAUST TO NEAREST
 WINDOW OR OPERATING DOOR. THE HOUSE PLAN CAN BE HAND
 DRAWN. A PLAN OF RECORD IS AVAILABLE FROM THE WPB
 BUILDING DEPARTMENT BY CONTACTING CRAIG MCPHERSON AT
 561-805-6684; EMAIL [email protected].
 7.PROVIDE SHUTOFF VALVE ON THE SUPPLY SIDE OF THE METER
 PER FBC FG 409.2.
 8.PER WPB FBC 107.2.1, ALL PLANS SHALL BE BEAR THE
 PRINTED NAME AND SIGNATURE OF THE DESIGNER.
  
 A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE REVIEW OF SUBMITTED CORRECTIONS.
  
 END OF COMMENTS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20041096 140 MONROE DR
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved