2020-05-14 13:51:34 | REVIEWED BY JERRY SMITH. |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| NFPA 54 = NATIONAL FUEL GAS CODE |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 20041096 140 MONROE DR |
| |
| GAS COMMENTS: DENIED |
| 1.SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE RANGE |
| PER FBC FG 304.1 |
| 2.SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| METER / MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE |
| BUILDING AND / OR SYSTEM FBC FG 402.4.1, 402.4.2 |
| 3.PER WPB FBC 107.2.1, SHOW PE TO GALVANIZED RIGID |
| PIPING TRANSITION ON RISER DIAGRAM. |
| 4.PER WPB FBC 107.2.1, PROVIDE THE MATERIAL AND TABLE |
| USED IN SIZING PIPING DOWNSTREAM OF MP REGULATOR(S). |
| INDICATE ON THE PLAN THE DISTANCE FROM REGULATOR TO |
| APPLIANCE. |
| 5.PER WPB FBC 107.2.1, PROVIDE DETAIL OF MP REGULATOR |
| WITH SHUTOFF VALVE, UNION AND OTHER REQUIRED |
| ACCESSORIES. COMPLY WITH FBC FG 410.2. |
| 6.PER WPB FBC 107.2.1, PROVIDE SITE W/BUILDING AND |
| POOL/DIMENSIONED BUILDING PLAN VIEW DRAWING SHOWING |
| BUILDING AND LAYOUT INCLUSIVE OF ROOMS, DOORS AND |
| WINDOWS, LOCATIONS OF GAS APPLIANCES, PIPE ROUTING AND |
| METER. INDICATE ON THE PLAN IF THE TANKLESS WATER |
| HEATER IS REPLACING AN EXISTING TANKLESS WATER HEATER |
| OR IS IT REPLACING A STORAGE TANK TYPE WATER HEATER OR |
| IS IT BEING ADDED TO THE EXISTING HOT WATER SYSTEM? |
| INDICATE ON THE APPLICATION IN THE DESCRIPTION OF WORK. |
| IF REPLACING OR SUPPLEMENTING, IDENTIFY AND SHOW |
| LOCATION OF THE EXISTING WATER HEATER. SHOW HORIZONTAL |
| DISTANCE FROM ANY OUTSIDE APPLIANCE EXHAUST TO NEAREST |
| WINDOW OR OPERATING DOOR. THE HOUSE PLAN CAN BE HAND |
| DRAWN. A PLAN OF RECORD IS AVAILABLE FROM THE WPB |
| BUILDING DEPARTMENT BY CONTACTING CRAIG MCPHERSON AT |
| 561-805-6684; EMAIL [email protected]. |
| 7.PROVIDE SHUTOFF VALVE ON THE SUPPLY SIDE OF THE METER |
| PER FBC FG 409.2. |
| 8.PER WPB FBC 107.2.1, ALL PLANS SHALL BE BEAR THE |
| PRINTED NAME AND SIGNATURE OF THE DESIGNER. |
| |
| A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME |
| AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED |
| UPON THE REVIEW OF SUBMITTED CORRECTIONS. |
| |
| END OF COMMENTS. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS |
| REQUIRED BY FAC AND FS. |
| ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| |
| |
| |