2020-05-06 11:11:04 | CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| |
| PLAN REVIEW - BUILDING |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER ? BUILDING - PX3169 |
| PLANS EXAMINER ? 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. CUSTOM DOORS SHALL COMPLY WITH FBC SEC. 1709.5. (SEE |
| EXCEPTION) |
| |
| |
| 1709.5 EXTERIOR WINDOW AND DOOR ASSEMBLIES. |
| THE DESIGN PRESSURE RATING OF EXTERIOR WINDOWS AND |
| DOORS IN BUILDINGS SHALL BE DETERMINED IN ACCORDANCE |
| WITH SECTION 1709.5.1 OR 1709.5.2. FOR THE PURPOSES OF |
| THIS SECTION, THE REQUIRED DESIGN PRESSURE SHALL BE |
| DETERMINED USING THE ALLOWABLE STRESS DESIGN LOAD |
| COMBINATIONS OF SECTION 1605.3. |
| |
| EXCEPTION: CUSTOM DOORS. CUSTOM (ONE-OF-A-KIND) |
| EXTERIOR DOOR ASSEMBLIES SHALL BE TESTED BY AN APPROVED |
| TESTING LABORATORY OR BE DESIGNED AND ENGINEERED IN |
| ACCORDANCE WITH ACCEPTED ENGINEERING PRACTICES BY A |
| FLORIDA REGISTERED DESIGN PROFESSIONAL. SIGNED AND |
| SEALED COPIES OF THE RATIONAL ANALYSIS AND CALCULATIONS |
| SHALL BE PROVIDED TO THE BUILDING OFFICIAL UPON PERMIT |
| APPLICATION. |
| |