Plan Review Notes
Plan Review Notes For Permit 20041085
Permit Number 20041085
Review Stop G
Sequence Number 2
Notes
Date Text
2020-07-27 13:57:4707/27/20 2ND GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE GAS TO THE GENERATOR IS 1/2 LBS BUT THE METER
 DOES NOT SPECIFY IF IT IS 2 PSI OR 1/2 LBS, PLEASE
 LABEL PER THE 2017 FBC RES. SEC. G2413.2.
  
 2. THE GENERATOR IS 16 KW AT FULL LOAD BTU 309 ON SPECS
 AND YOU HAVE 240 BTU'S ON ISOMETRIC PLEASE CHANGE TO
 REFLECT TOTAL BTU'S AND RECALCULATE PER THE 2017 FBC
 RES. SEC. G2413.
  
 3. PLEASE SHOW AND LABEL DRIP LEG, SHUT OFF VALVE,
 UNION AND REGULATOR PER THE 2017 FBC RES. SEC.
 G2401.1.3.
  
 4. THE GENRAC REQUIRES 5" TO 7" WATER COLUMN THIS NEED
 TO BE REGULATED, PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES.
 SEC. G2421.1.
  
 5. PEASE DELETE THE COMMENT OF THE TANK AT BOTTOM OF
 PAGE PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  