Date |
Text |
2020-05-19 13:59:17 | |
| 1ST REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT #20041083 |
| 5/19/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) GAS RISER: |
| A) CORRECT THE 329 MBH GAS LOAD FOR THE GENERATOR. THE |
| SPECS INDICATE 306MBH- SECTION 107.2.1 WPB. |
| B) CORRECT THE TOTAL LOAD- 413 MBH- SECTION G2413.2 FBC |
| RES. |
| C) LIST ALL TABLES USED FOR SIZING THE GAS PIPING- SEE |
| TABLES G2413.4(1) THROUGH G2413.4(21) FBC RES. |
| |
| 2) SURVEY: THE GENERATOR SHALL BE LOCATED A MINIMUM OF |
| 5' FROM THE ADJACENT EXTERIOR WALL, OR THE WALL SHALL |
| HAVE A 1-HR. FIRE RESISTANCE RATING- SECTION 4.1.4 (1) |
| NFPA 37. THE GENERATOR SHALL ALSO HAVE A 10' CLEARANCE |
| DISTANCE FROM AIR INTAKES AND OPERABLE OPENINGS INTO |
| THE BUILDING- SECTION R303.5.1 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |