Plan Review Notes
Plan Review Notes For Permit 20041083
Permit Number 20041083
Review Stop G
Sequence Number 1
Notes
Date Text
2020-05-19 13:59:17 
 1ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT #20041083
 5/19/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER:
 A) CORRECT THE 329 MBH GAS LOAD FOR THE GENERATOR. THE
 SPECS INDICATE 306MBH- SECTION 107.2.1 WPB.
 B) CORRECT THE TOTAL LOAD- 413 MBH- SECTION G2413.2 FBC
 RES.
 C) LIST ALL TABLES USED FOR SIZING THE GAS PIPING- SEE
 TABLES G2413.4(1) THROUGH G2413.4(21) FBC RES.
  
 2) SURVEY: THE GENERATOR SHALL BE LOCATED A MINIMUM OF
 5' FROM THE ADJACENT EXTERIOR WALL, OR THE WALL SHALL
 HAVE A 1-HR. FIRE RESISTANCE RATING- SECTION 4.1.4 (1)
 NFPA 37. THE GENERATOR SHALL ALSO HAVE A 10' CLEARANCE
 DISTANCE FROM AIR INTAKES AND OPERABLE OPENINGS INTO
 THE BUILDING- SECTION R303.5.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  