2020-07-06 10:05:51YOUR SUBMITTAL IS NOT APPROVED FOR THE FOLLOWING
 REASONS:
 1) THE ELECTRONICALLY SUBMITTED GENERATOR PAD
 ENGINEERING DOES NOT HAVE THE ENGINEER'S DIGITAL
 SIGNATURE AS REQUIRED BY FS 471 AND FAC 61G15.
 2) THE PAD ENGINEERING HAS A STATEMENT WHICH REQUIRES
 JOB SPECIFIC CALCULATIONS TO DETERMINE THE REQUIRED
 WIND LOAD PRESSURES AT THE INSTALLATION LOCATION. FBC
 107
  
  