2020-06-03 10:42:201ST REVIEW FBC-2017 MECHANICAL
 PERMIT -20041081
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REMOVE OPTIONAL EQUIPMENT AND GAS LINE FROM THIS
 DRAWING OR INCLUDE THIS EQUIPMENT AND SPECS FOR THIS
 EQUIPMENT UNDER THIS PERMIT.. THE PERMIT WILL NOT BE
 FOR OPTIONAL EQUIPMENT. FBC FS 107.2.1
  
 2) IT APPEARS THAT YOU ARE CUTTING THE EXISTING PIPE
 CLOSE TO THE METER AND INSTALLING A ?T? FITTING. PLEASE
 PROVIDE THE TYPE OF MATERIAL FOR EXISTING GAS PIPE IN
 THIS LOCATION. PLEASE ALSO SHOW THE SIZE OF THIS PIPE,
 PLEASE UNDERSTAND THAT THIS SHORT PIPE MUST BE SIZED
 FOR THE ENTIRE GAS LOAD OF THE METER AS IT IS SUPPLYING
 THE EXISTING HOUSE LOAD PLUS THE NEW LOAD OF THE
 GENERATOR. PLEASE INCLUDE THE GAS TABLE THAT IS USED TO
 SIZE THIS PIPE. FBC FG 402.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  