2020-06-03 10:42:20 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT -20041081 |
| |
| CODES IN EFFECT: |
| |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) REMOVE OPTIONAL EQUIPMENT AND GAS LINE FROM THIS |
| DRAWING OR INCLUDE THIS EQUIPMENT AND SPECS FOR THIS |
| EQUIPMENT UNDER THIS PERMIT.. THE PERMIT WILL NOT BE |
| FOR OPTIONAL EQUIPMENT. FBC FS 107.2.1 |
| |
| 2) IT APPEARS THAT YOU ARE CUTTING THE EXISTING PIPE |
| CLOSE TO THE METER AND INSTALLING A ?T? FITTING. PLEASE |
| PROVIDE THE TYPE OF MATERIAL FOR EXISTING GAS PIPE IN |
| THIS LOCATION. PLEASE ALSO SHOW THE SIZE OF THIS PIPE, |
| PLEASE UNDERSTAND THAT THIS SHORT PIPE MUST BE SIZED |
| FOR THE ENTIRE GAS LOAD OF THE METER AS IT IS SUPPLYING |
| THE EXISTING HOUSE LOAD PLUS THE NEW LOAD OF THE |
| GENERATOR. PLEASE INCLUDE THE GAS TABLE THAT IS USED TO |
| SIZE THIS PIPE. FBC FG 402. |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |