Plan Review Notes For Permit 20041081 |
Permit Number |
20041081 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-05-22 07:53:43 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT GENERATOR PAD PLANS. SPECIFY THE PAD | | DIMENSIONS, REINFORCING AND SPECIFY HOW THE GENERATOR | | WILL BE ANCHORED TO THE PAD. SPECIFY THE TYPE, SIZE AND | | LOCATIONS OF THE FASTENERS. FBC 107.2.1 |
|